CEASEFIRE™ Coatings Test Results
CEASEFIRE™ coatings have proven themselves in third-party testing labs as capable protective coatings against extreme heat and fire. Below we list the tests that our coatings have passed to date. We aim to be able to provide more test results in the future.ASTM E-84
Waterborne Epoxy: Class A
High Performance: Class A
Clear: Class A
UL-1709
Waterborne Epoxy: 25 min @ 32 mils
Latex: 13 min @ 25 mils
ASTM E-119
Waterborne Epoxy: 1 hr 20 min @ 3/16"
Superior: 56 min @ 60 mils
High Performance: 52 min @ 35 mils / 58 min @ 60 mils
Structural Steel: 114 min @ 1/4-3/8" / 139 min @ 3/8-1/2"
UL94
Latex (over polyethylene foam): V0
Latex (over polypropylene foam): V0
IMO A.653(16)
Superior: Pass @ 10 mils
ASTM B117
Superior: 500 hours, no coating loss
Structural Steel: 720 hours, no coating loss
ASTM D695
Structural Steel: 1/2" - 892.4 psi
ASTM D256
Structural Steel: 1/2" - .93 ft-lbs-force/in.
ASTM E662
Structural Steel:
DS @ 1.5 min: 0.5 (non flaming), 1.7 (flaming)
DS @ 4.0 min: 1.1 (non flaming), 51.7 (flaming)
Dm(corr): 68.7 (non flaming), 205.5 (flaming)
ASTM D4541
Structural Steel: 125 mils - 275 psi
BSS 7239
Structural Steel:
Gas: Avg. ppm
CO: 325.0
HCN: 20.0
SO2: 10.0
HCL: 27.5
HF: 0.0
NO: 57.5
NO2: 8.0
ASTM G53
Structural Steel: No cracking, melting, or spotting
ASTM E162
Structural Steel: Class A
MSC.41(64)
Superior:
Gas: 25kw-nf/25kw-f/50kw-nf/Reg. limit
CO: 30/80/300/1450
HCN: 10/14/14/140
SO2: 0/10/10/120
HCL: 10/1/0.4/600
HF: 0/0/0/600
NOx: 0/21/12/350